The QNDB7 AC Current Sensor Transmitter measures AC current using electromagnetic induction (mutual inductance). This version is rated at 20A and has a measuring range up to 24A. It runs on +24V and gives a 4-20mA output with RS485 communication. It has galvanic isolation of 2.5 kV between the primary and secondary circuits, ≤ 0.5% accuracy and a response time under 200 ms, so readings stay reliable and electrically separated. It is small, easy to mount, adds no insertion losses and has high immunity to external interference. It suits variable speed drives, welding machines, UPS systems and battery-supplied applications.
حساس ومحوّل تيار متردد QNDB7 يقيس التيار المتردد (AC) بمبدأ الحث الكهرومغناطيسي (الحث المتبادل). هذا الإصدار تياره المقنن 20 أمبير ومدى قياسه يصل إلى 24 أمبير. يعمل على جهد +24 فولت ويعطي خرج 4-20 مللي أمبير مع اتصال RS485. فيه عزل كهربائي (Galvanic Isolation) بقوة 2.5 كيلو فولت بين الدائرة الابتدائية والثانوية، ودقة ≤ 0.5%، وزمن استجابة أقل من 200 مللي ثانية، فتبقى القراءات موثوقة ومعزولة كهربائياً. حجمه صغير وتركيبه سهل، ولا يسبب أي فقد في الإدخال، ومقاوم بدرجة عالية للتداخل الخارجي. يناسب محركات السرعة المتغيرة وماكينات اللحام وأنظمة UPS والتطبيقات التي تعمل على البطاريات.
The QNDB7 Series AC Current Sensor / Current Transmitter measures AC currents electronically and accurately. It works on electromagnetic induction (mutual inductance), and the galvanic isolation between the primary (measured) circuit and the secondary (output) circuit keeps the measuring system electrically separated from the load.
This model is rated at 20A (Ipn) and measures up to 24A (Ip). It runs on a +24V (±5%) supply and gives a 4-20mA output with RS485 communication. Accuracy is ≤ 0.5%, linearity is ≤ 1% FS, response time is under 200 ms and bandwidth is 40 to 6000 Hz. It withstands 2.5 kV isolation (50Hz, 1 min) and works from -20°C to +80°C.
How to use: pass the conductor carrying the current through the sensor, and the output is read at the output terminals. Wrong wiring can damage the sensor. The output amplitude can be adjusted to the user’s requirements, and custom versions with other rated input currents and outputs can be designed.
Pin Connection:
Specifications
| Parameter | Value |
|---|---|
| Model | QNDB7 |
| Rated Current (Ipn) | 20 A |
| Measuring Range (Ip) | 24 A |
| Rated Output (Io) | 4-20 mA / RS485 |
| Supply Voltage | +24 V (±5%) |
| Load Resistance | ≥ 250 Ω |
| Accuracy | ≤ 0.5 % |
| Linearity | ≤ 1 %FS |
| Quiescent Current Consumption | < 30 mA |
| Offset Current | ±0.1 mA |
| Offset Current Drift | ≤ 0.005 mA/°C |
| Response Time | < 200 ms |
| Bandwidth | 40 ~ 6000 Hz |
| Galvanic Isolation | 2.5 kV (50Hz, 1 min) |
| Measuring Principle | Electromagnetic induction (mutual inductance) |
| Operating Temperature | -20 to +80 °C |
| Storage Temperature | -40 to +85 °C |
| Mass (approx.) | 85 g |
| Standards | SJ 20790-2000; JB/T 7490-2007 |
| Test Conditions | Ta = 25°C ±5°C |
Applications