The QNDB7 AC Current Sensor Transmitter measures AC currents with a rated current of 100A and a measuring range of up to 120A. It works on electromagnetic induction (mutual inductance), with galvanic isolation between the primary and secondary circuits. It runs on a +24V supply and gives a 4-20mA output with RS485 output. It has ≤0.5% accuracy, ≤1% FS linearity, a 40~6000 Hz bandwidth and 2.5 kV isolation. It suits variable speed drives, welding machines, UPS systems and battery-supplied applications. It is small, easy to mount and highly immune to external interference.
حساس ومحوّل التيار المتردد QNDB7 يقيس التيار المتردد (AC) بـتيار مقنن 100A ومدى قياس يصل إلى 120A. يعمل بمبدأ الحث الكهرومغناطيسي (الحث المتبادل)، مع عزل جلفاني بين الدائرة الابتدائية والدائرة الثانوية. يعمل على جهد تغذية +24V ويعطي خرج 4-20mA مع خرج RS485. دقته ≤0.5%، وخطيته ≤1% FS، ونطاقه الترددي 40~6000 Hz، وعزله 2.5 kV. يناسب محركات السرعة المتغيرة وماكينات اللحام وأنظمة UPS والتطبيقات التي تعمل على البطاريات. صغير الحجم وسهل التركيب ومقاوم بدرجة عالية للتداخل الخارجي.
The QNDB7 Series AC Current Sensor / Current Transmitter measures AC currents electronically and accurately. It works on electromagnetic induction (mutual inductance), and galvanic isolation separates the primary circuit (the measured current) from the secondary circuit (the output), so the measured line and the monitoring electronics stay electrically apart.
This model has a rated current of 100A and a measuring range of up to 120A. It runs on a +24V (±5%) supply and gives a 4-20mA output with RS485 output. The output needs a load resistance of at least 250Ω. Performance figures are ≤0.5% accuracy, ≤1% FS linearity, a response time under 200 ms and a bandwidth of 40~6000 Hz. Offset current is ±0.1 mA, with offset current drift of ≤0.005 mA/℃.
The sensor has 2.5 kV isolation (50 Hz, 1 min). It works from -20 to +80℃ and can be stored from -40 to +85℃. It weighs about 85 g and meets SJ 20790-2000 and JB/T 7490-2007.
Wiring: Pin 1: +24V, Pin 2: GND, Pin 3: Iout, Pin 4: GND. Note: wrong wiring may damage the sensor.
The output amplitude can be adjusted to suit the user, and custom designs with other rated input currents and outputs are available.
Specifications
| Parameter | Value |
|---|---|
| Model | QNDB7 |
| Measured Current Type | AC |
| Measuring Principle | Electromagnetic induction (mutual inductance) |
| Rated Current (Ipn) | 100 A |
| Measuring Range (Ip) | 120 A |
| Output | 4-20 mA / RS485 |
| Supply Voltage | +24 V (±5%) |
| Load Resistance | ≥ 250 Ω |
| Accuracy | ≤ 0.5 % |
| Linearity | ≤ 1 %FS |
| Quiescent Current Consumption | < 30 mA |
| Offset Current | ±0.1 mA |
| Offset Current Drift | ≤ 0.005 mA/℃ |
| Response Time | < 200 ms |
| Bandwidth | 40 ~ 6000 Hz |
| Galvanic Isolation | 2.5 kV (50 Hz, 1 min) |
| Operating Temperature | -20 to +80 ℃ |
| Storage Temperature | -40 to +85 ℃ |
| Weight (approx.) | 85 g |
| Pinout | 1: +24V, 2: GND, 3: Iout, 4: GND |
| Standards | SJ 20790-2000, JB/T 7490-2007 |
Applications