The QNDBK2-16 Split Core AC Current Sensor Transmitter measures AC current under electrical isolation using the principle of electromagnetic induction. It outputs a 4-20mA DC current proportional to the effective (RMS) value of the measured current. This model is rated for 50A AC with a measuring range up to 60A, and works from a +12V to +24V supply. It offers ≤0.5% accuracy, ≤0.2% FS linearity, 3kV galvanic isolation, and a simple 2-wire connection. Its split core design, small size, easy mounting, and high immunity to external interference suit power supplies, UPS systems, IoT, and electrochemical applications.
يقيس حساس وناقل التيار المتردد QNDBK2-16 ذو القلب المنفصل (Split Core) التيار المتردد في ظل عزل كهربائي بالاعتماد على مبدأ الحث الكهرومغناطيسي. ويعطي خرج تيار مستمر 4-20mA يتناسب مع القيمة الفعالة (RMS) للتيار المقاس. هذا الموديل مصمم لتيار مقنن 50A AC بمدى قياس يصل إلى 60A، ويعمل بجهد تغذية من +12V إلى +24V. يتميز بدقة ≤0.5% وخطية ≤0.2% FS وعزل كهربائي يصل إلى 3kV وتوصيل بسيط بسلكين فقط. كما أن تصميم القلب المنفصل وصغر الحجم وسهولة التركيب والمناعة العالية ضد التداخلات الخارجية تجعله مناسباً لمزودات الطاقة وأنظمة UPS وتطبيقات إنترنت الأشياء والتطبيقات الكهروكيميائية.
The QNDBK2-16 Series Split Core AC Current Sensor / Transmitter applies the principle of electromagnetic induction to measure AC signal current under electrical isolation conditions. It produces a 4-20mA DC current output proportional to the effective value of the measured current, which makes it a convenient interface to controllers, data acquisition systems, and monitoring equipment.
This model is rated at 50A AC (Ipn) with a measurement range of up to 60A AC (Ip). It operates from a +12V to +24V supply and uses a simple 2-wire connection. It offers ≤0.5% accuracy, ≤0.2% FS linearity, a zero current of 4 ±0.1mA, and an offset drift of ≤±0.05mA/°C. Its bandwidth is 20 to 2000Hz, and its power consumption is less than 7mA + Is.
The transmitter provides 3kV galvanic isolation (50Hz, 1 min), operates from -20°C to +70°C, and weighs about 75g. It is manufactured to the Q/320115QHKJ01-2013 standard.
To use it, pass the current to be measured through the transmitter, and the output current is read at the output end. Correct wiring is essential, as wrong wiring may damage the transmitter. The output amplitude can be adjusted according to user requirements, and custom designs with different rated input currents and output currents are available.
Pin Connections (2-wire type):
Specifications (Ta = 25°C ±5°C)
| Parameter | Value |
|---|---|
| Model | QNDBK2-16 |
| Type | Split core AC current sensor / transmitter |
| Measuring Principle | Electromagnetic induction |
| Rated Current (Ipn) | 50A AC |
| Measure Range (Ip) | 60A AC |
| Rated Output | 4-20mA DC |
| Supply Voltage | +12V to +24V |
| Accuracy | ≤ 0.5% |
| Linearity | ≤ 0.2% FS |
| Power Consumption | < 7mA + Is |
| Zero Current | 4 ±0.1mA |
| Bandwidth | 20 – 2000Hz |
| Offset Drift | ≤ ±0.05mA/°C |
| Galvanic Isolation | 3kV (50Hz, 1 min) |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -25°C to +85°C |
| Mass (approx.) | 75g |
| Standard | Q/320115QHKJ01-2013 |
| Wiring | 2-wire: Pin 1: 4-20mA, Pin 2: +24V |
Applications