Description:
8Digital Input + 4Digital Output (Power Relay) Ethernet ModBus-TCP Remote Terminal Unit
Remote Ethernet I/O Modbus module, support TCP/IP protocol, through the Ethernet interface with other Modbus TCP/IP protocol. Ethernet also supports 8 independent TCP communication connection.
Type | A-1860 | |
Operation Voltage | 10 ~ 30VDC/24VAC | |
Inputs | 8 * Isolation DI | Status Low:<1VDC |
Status High:>5~30VDC | ||
Outputs | 4, Power Relay | |
Continuous Current | 250VAC(7A)/ 30VDC(7A) | |
Ethernet | 10/100Mbps | |
Isolation | YES(5000VDC) | |
Input Operating Frequency | 10Hz | |
Output Operating Frequency | 10Hz | |
Operation Temperature | -20 to +75℃ | |
Degree Of Protection | IP20 | |
Installation | 35 mm DIN rail / Flush mounting | |
Dimension (W×H×D) | 76.4*118.2*38.5 mm | |
Analog Inputs | - | |
Analog Input Type | - | |
Analog Outputs | - | |
Analog Output Type | - | |
Input Impedance | - | |
Analog Input / Output Accuracy | - | |
Interface | Ethernet + USB | |
Channel Independent Configuration | Yes | |
Sampling Rate | 10 sample/second (Total) | |
CMR @ 50/60 Hz | 120 dB | |
Span Drift | ±50 ppm/℃ | |
Zero Drift | ±18 μV/℃ |
Features:
v Ethernet Interface + USB Interface
v Supports 8 Independent Sockets Simultaneously
v Built-in Step Motor Driver, Connect Directly
v Output Over Current Protection (OCP)
v Output Over Thermal Protection (OTP)
v Output Under Voltage Lockout (UVLO)
v Support MODBUS TCP/IP
v Flexible User-defined Modbus address
v Support LAN 10/100 Mbps Communication Rate
v Free monitor PC software "Utility"